2CDS283001R0255

S203P-B25 Miniature Circuit Breaker B-Char.,25kA,25A,3P

Manufacturer's No: S203PB25     Manufacturer: ABB
S203P-B25 Miniature Circuit Breaker B-Char.,25kA,25A,3P

Availability On Request

POA

This product has been superseded by

2CDS383001R0255

Please check compatibility before purchasing.

  • Miniature Circuit Breaker S203P-B25, 25A, 3P, B-Char.
  • Current limiting with delayed thermal tripping mechanism for overload protection
  • Electromechanic tripping mechanism for short circuit protection
  • Available in different characteristics: B, C, D, K, Z
  • Configurations: 1P, 1P+N, 2P, 3P, 3P+N, 4P
  • Breaking capacity: up to 25 kA at 230/400 V AC
  • Rated currents: up to 63A
  • Complies with IEC/EN 60898-1, IEC/EN 609 47-2, UL1077, and CSA 22.2 No. 235
  • Suitable for residential, commercial, and industrial applications
  • Bottom-fitting auxiliary contact available for space-saving (50% space saved)
 

Product

Manufacturer Material ID -
S203PB25
Net Weight -
0.42kg

Additional Product Information

Country of Origin -
DE
Minimum Order Quantity -
1
UNSPSC -
39121601

Technical Specification

Built-in depth -
69 Millimetre
Release characteristic -
B
Degree of protection (IP) -
IP20
Voltage type -
AC
Recess depth -
69 Millimetre
Rated current -
25 Ampere
Rated voltage -
400 Volt
Frequency -
50 Hertz
Tripping characteristic (type/curve) -
B
Rated insulation voltage Ui -
440 Volt
Current limiting class -
3
Over voltage category -
3
Pollution degree -
3
Width in number of modular spacings -
3
Degree of protection (IP rating) -
IP20
Number of protected poles -
3
Connectable conductor cross section solid-core -
0.75 Square millimetre
Connectable conductor cross section multi-wired -
0.75 Square millimetre
Ambient temperature during operating -
-25 Degrees celsius
Additional equipment possible -
Number of poles (total) -
3
Rated short-circuit breaking capacity Icn EN 60898 at 400 V -
25 kiloampere
Rated short-circuit breaking capacity Icn EN 60898 at 230 V -
12.5 kiloampere
Rated short-circuit breaking capacity Icu IEC 60947-2 at 230 V -
25 kiloampere
Rated short-circuit breaking capacity Icu IEC 60947-2 at 400 V -
25 kiloampere
Rated impulse-withstand voltage (Uimp) -
4 Kilovolt
ABB

Availability On Request

POA
Sign in or Register for customer prices.

This product has been superseded by

2CDS383001R0255

Please check compatibility before purchasing.

Additional Information

Data Sheets

Did you know, we are an entrusted Siemens approved partner?

Loading...