3VL27101DC338RD1

circuit breaker VL160N standard breaking capacity Icu=55kA, 415V AC 3-pole, line protection Electron

Manufacturer's No: 3VL2710-1DC33-8RD1     Manufacturer: Siemens
circuit breaker VL160N standard breaking capacity Icu=55kA, 415V AC 3-pole, line protection Electron

Availability On Request

POA
  • Circuit Breaker VL160N
    • Standard Breaking Capacity: Icu = 55kA
    • Voltage: 415V AC
    • Configuration: 3-pole
    • Line Protection: Electronic Trip Unit TM
    • Rated Current: IR = 80-100A
    • Overload Protection: II = 500-1000A
    • Shunt Release: 110-127V AC
    • Auxiliary/Alarm Switch Mounting Kit
      • 2 AUX (1 NO + 1 NC)
      • 1 AS (1 NO)
 

Product

Manufacturer Material ID -
3VL2710-1DC33-8RD1
Net Weight -
2.57kg

Additional Product Information

Commodity Code -
85362090
Country of Origin -
DE
Export Control Regulations -
EAR99 / N
Minimum Order Quantity -
1
UNSPSC -
39121601

Technical Specification

Complete device with protection unit -
Degree of protection (IP rating) -
IP20
Device construction -
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional -
Motor drive optional -
Number of auxiliary contacts as change-over contact -
0
Number of auxiliary contacts as normally closed contact -
1
Number of auxiliary contacts as normally open contact -
2
Number of poles -
3
Power loss -
27 Watt
Rated short-circuit breaking capacity Icu at 400 V, 50 Hz -
55 kiloampere
Suitable for DIN rail (top hat rail) mounting -
Switched-off indicator available -
Type of electrical connection of main circuit -
Frame clamp