3VL67801SE362GC1

circuit breaker VL800N standard breaking capacity Icu=55kA, 415V AC 3-pole, line protection trip uni

Manufacturer's No: 3VL6780-1SE36-2GC1     Manufacturer: Siemens
circuit breaker VL800N standard breaking capacity Icu=55kA, 415V AC 3-pole, line protection trip uni

Availability On Request

POA
  • Circuit breaker VL800N
  • Standard breaking capacity: Icu = 55kA at 415V AC
  • 3-pole with line protection trip unit ETU20
  • Long-time and short-time delay overload protection
  • Rated current In = 800A, adjustable from 320A to 800A
  • Short-circuit protection: II = 8 x In
  • Undervoltage release: 110-127V AC
  • Auxiliary switch mounting kit: 4 AUX (2 NO + 2 NC)
 

Product

Manufacturer Material ID -
3VL6780-1SE36-2GC1
Net Weight -
16.00kg

Additional Product Information

Commodity Code -
85362090
Country of Origin -
MX
Export Control Regulations -
EAR99 / N
Minimum Order Quantity -
1
UNSPSC -
39121601

Technical Specification

Complete device with protection unit -
Degree of protection (IP rating) -
IP20
Device construction -
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional -
Motor drive optional -
Number of auxiliary contacts as change-over contact -
0
Number of auxiliary contacts as normally closed contact -
2
Number of auxiliary contacts as normally open contact -
2
Number of poles -
3
Power loss -
250 Watt
Rated short-circuit breaking capacity Icu at 400 V, 50 Hz -
55 kiloampere
Suitable for DIN rail (top hat rail) mounting -
Type of electrical connection of main circuit -
Screw connection
With integrated under voltage release -

Availability On Request

POA