3RV11424AA10

Circuit breaker size S3 for motor protection, Class 10 with overload relay function A-release 11...1

Manufacturer's No: 3RV1142-4AA10     Manufacturer: Siemens
Circuit breaker size S3 for motor protection, Class 10 with overload relay function A-release 11...1

Availability On Request

POA

This product has been superseded by

3RV21314TA10

Please check compatibility before purchasing.

  • Circuit breaker size: S3
  • Motor protection class: Class 10
  • Overload relay function with A-release: 11...16 A
  • Short-circuit release: 208 A
  • Screw terminal
  • Increased switching capacity
  • Phased-out product
  • Successor model: SIRIUS 3RV2
  • Preferred successor type: 3RV2131-4TA10
 

Product

Manufacturer Material ID -
3RV1142-4AA10
Net Weight -
2.25kg

Additional Product Information

Commodity Code -
85362010
Country of Origin -
DE
Export Control Regulations -
N / N
Minimum Order Quantity -
1
UNSPSC -
39121601

Technical Specification

Switch off technique -
UN
Rated operation power at AC-3, 230 V -
- Kilowatt
Adjustment range undelayed short-circuit release -
- Ampere
Device construction -
UN
Width -
70 Millimetre
Height -
165 Millimetre
Depth -
174 Millimetre
Rated operation power at AC-3, 400 V -
7.5 Kilowatt
Rated permanent current Iu -
16 Ampere
Number of poles -
3
Rated operating voltage -
690 Volt
Overload release current setting -
11 Ampere
Degree of protection (IP) -
IP20
Type of electrical connection of main circuit -
Screw connection
Type of control element -
Turn button
Rated short-circuit breaking capacity lcu at 400 V, AC -
100 kiloampere
Phase failure sensitive -

Availability On Request

POA
Sign in or Register for customer prices.

This product has been superseded by

3RV21314TA10

Please check compatibility before purchasing.