3VA21407JQ420AA0

circuit breaker 3VA2 IEC Frame 160 breaking capacity class C Icu=110 kA @ 415 V 4-pole, line protection ETU560, LSIG, In=40 A over

Manufacturer's No: 3VA2140-7JQ42-0AA0     Manufacturer: Siemens
circuit breaker 3VA2 IEC Frame 160 breaking capacity class C Icu=110 kA @ 415 V 4-pole, line protection ETU560, LSIG, In=40 A overload protection I...

Availability On Request

£1,284.42
  • Circuit breaker 3VA2 IEC Frame 160
  • Breaking capacity class C: Icu=110 kA @ 415 V
  • 4-pole, line protection ETU560, LSIG
  • Rated current In=40 A, overload protection Ir=16 A...40 A
  • Short-circuit protection Isd=0.6..10x In, Ii=1.5..12x In
  • Neutral conductor protection adjustable up to 160%
  • Ground-fault protection with switch-off capability Ig=0.4...1 x In, tg=0.05-0.8s
  • Nut keeper kit included

Accessories

Presentation video
Question and Answer (Q&A video)
Product video
Presentation video
Question and Answer (Q&A video)
Product video
 

Product

Manufacturer Material ID -
3VA2140-7JQ42-0AA0
Net Weight -
2.94kg

Additional Product Information

Commodity Code -
85362010
Country of Origin -
CZ
RoHs Compliance -
Yes
UNSPSC -
39121601

Technical Specification

Degree of protection (IP) -
IP40
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz -
110 kiloampere
Adjustment range short-term delayed short-circuit release -
24 Ampere
Adjustment range undelayed short-circuit release -
60 Ampere
Complete device with protection unit -
Degree of protection (IP rating) -
IP40
Device construction -
Built-in device fixed built-in technique
Integrated earth fault protection -
Motor drive optional -
Number of auxiliary contacts as change-over contact -
0
Number of auxiliary contacts as normally closed contact -
0
Number of auxiliary contacts as normally open contact -
0
Number of poles -
4
Overload release current setting -
16 Ampere
Position of connection for main current circuit -
Front
Power loss -
1.6 Watt
Rated permanent current Iu -
40 Ampere
Rated short-circuit breaking capacity Icu at 400 V, 50 Hz -
110 kiloampere
Rated voltage -
690 Volt
Type of control element -
Rocker lever
Type of electrical connection of main circuit -
Screw connection

Availability On Request