3VL27103TA460AD1

circuit breaker VL160L very high breaking capacity Icu=100kA, 415V AC 4-pole, line protection Electr

Manufacturer's No: 3VL2710-3TA46-0AD1     Manufacturer: Siemens
circuit breaker VL160L very high breaking capacity Icu=100kA, 415V AC 4-pole, line protection Electr

Availability On Request

POA
  • Circuit breaker VL160L
    • Very high breaking capacity: Icu=100kA, 415V AC
    • 4-pole, line protection
    • Electronic Trip Unit ETU10
      • LIN In=100A
      • Rated current IR=40...100A
      • Overload protection: II=1.25 to 11xIN
      • Short-circuit protection
    • N protected with screw terminals
    • Auxiliary/alarm switch mounting kit
      • 2 AUX (1 NO+1 NC) + 1 AS (1 NO)
 

Product

Manufacturer Material ID -
3VL2710-3TA46-0AD1
Net Weight -
3.10kg

Additional Product Information

Commodity Code -
85362090
Country of Origin -
DE
Export Control Regulations -
EAR99 / N
Minimum Order Quantity -
1
UNSPSC -
39121601

Technical Specification

Complete device with protection unit -
Degree of protection (IP rating) -
IP20
Device construction -
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional -
Motor drive optional -
Number of auxiliary contacts as change-over contact -
0
Number of auxiliary contacts as normally closed contact -
1
Number of auxiliary contacts as normally open contact -
2
Number of poles -
4
Power loss -
16 Watt
Rated short-circuit breaking capacity Icu at 400 V, 50 Hz -
100 kiloampere
Suitable for DIN rail (top hat rail) mounting -
Switched-off indicator available -
Type of electrical connection of main circuit -
Screw connection

Availability On Request

POA
Sign in or Register for customer prices.

Additional Information

Did you know, we are an entrusted Siemens approved partner?

Loading...