3WA11162AB404EQ0-Z R57+T40

Withdrawable circuit breaker without guide frame, IEC 60947-2, frame size 1, 4-poles, N-pole left, In=1600A up to 690V AC 50/60Hz,

Manufacturer's No: 3WA1116-2AB40-4EQ0-Z R57+T40     Manufacturer: Siemens
Withdrawable circuit breaker without guide frame, IEC 60947-2, frame size 1, 4-poles, N-pole left, In=1600A up to 690V AC 50/60Hz, breaking capacity N Icu=55/42kA at 500/690V, Trip unit ETU300 LSI opt

Availability On Request

£10,891.56
  • Withdrawable circuit breaker without guide frame
  • Complies with IEC 60947-2
  • Frame size: 1
  • 4-poles, N-pole left
  • Rated current (In): 1600A
  • Voltage: Up to 690V AC, 50/60Hz
  • Breaking capacity (N Icu): 55/42kA at 500/690V
  • Trip unit: ETU300 LSI optimized for standard applications
  • Protection types: LT, ST, INST
  • Includes N-protection with internal N-sensor available

Read more

  • Includes trip alarm switch (1xCO)
  • Lacks communication and metering function
  • Operating mechanism: Manual and motorized (M) 208-240 V AC / 220-250 V DC
  • Storage status and ready-to-close signaling switches
  • Auxiliary switches: 2NO+2NC
  • Closing coil (CC): 100% OP 208-240 V AC / 220-250 V DC, applicable for continuous duty
  • Lacks remote trip alarm reset coil (RR)
  • Undervoltage release (UVR): Instantaneous (0.08 s) and short-delay (0.2 s), 208-240 V AC / 220-250 V DC
  • Lacks 1st shunt trip option
  • Option R57: Mutual mechanical interlocking with 2 m Bowden cable for withdrawable circuit breakers without guide frame; ordered per breaker separately
  • Option T40: Door sealing frame IP41
 

Product

Manufacturer Material ID -
3WA1116-2AB40-4EQ0-Z R57+T40
Net Weight -
56.65kg

Additional Product Information

Commodity Code -
85362090
Country of Origin -
CZ
Export Control Regulations -
AL:N / ECCN:EAR99
UNSPSC -
39121601

Availability On Request