3WL11163EG471BA2-Z K07+M06+M21+R21+R30+T40

withdrawable circuit breaker with guide frame 4-pole, size I, IEC In=1600A to 690V, AC50/60Hz Icu=66kA at 500V rear connection ver

Manufacturer's No: 3WL1116-3EG47-1BA2-Z K07+M06+M21+R21+R30+T40     Manufacturer: Siemens
withdrawable circuit breaker with guide frame 4-pole, size I, IEC In=1600A to 690V, AC50/60Hz Icu=66kA at 500V rear connection vertical Overcurrent release ETU 45 LSING protection adjustable 0.4-1 in

Availability On Request

£17,404.09
  • Withdrawable circuit breaker with guide frame
  • 4-pole, size I, IEC rated at In=1600A to 690V AC 50/60Hz
  • Icu=66kA at 500V
  • Overcurrent release ETU 45 LSING protection adjustable from 0.4-1
  • Rear connection vertical
  • Ground fault protection
  • Manual operating mechanism with storage and mechanical request
  • 1st auxiliary release Shunt release "F", F1 24V DC
  • Tripped signaling contact K07
  • Motor drive M06: AC 50/60Hz 208-240V or 220-250V DC

Read more

  • Switch-on solenoid M21: 24V DC
  • Shutter R21: 2-part, lockable with bracket lock
  • Locking device R30 against opening of the control cabinet door
  • Door sealing frame T40
 

Product

Manufacturer Material ID -
3WL1116-3EG47-1BA2-Z K07+M06+M21+R21+R30+T40
Net Weight -
84.00kg

Additional Product Information

Commodity Code -
85362090
Country of Origin -
CZ
Export Control Regulations -
EAR99 / N
UNSPSC -
39121601

Availability On Request

£17,404.09
Sign in or Register for customer prices.

Additional Information

Did you know, we are an entrusted Siemens approved partner?

Loading...