HMI

Overview

Basic Panels (1st Generation)

  • Ideal entry-level series from 3″ to 15″ for operator control and monitoring of compact machines and systems
  • Clear process representation thanks to use of pixel-graphics displays
  • Intuitive operation using touch and tactile function keys
  • Equipped with all the necessary basic functions such as alarm logging, recipe management, plots, vector graphics, and language switching
  • Simple connection to the controller via integral Ethernet interface or separate version with RS 485/422
  • Faster commissioning thanks to integrated diagnostics viewer and IP setting for SIMATIC S7-1200 and S7-1500 PLCs

Benefits

  • Integral component of Totally Integrated Automation (TIA):
    Increased productivity, minimum engineering overhead, reduction in life-cycle costs

    • Can be used even where installation space is restricted thanks to vertical configuring (4″ and 6″ devices)
    • Short configuring and commissioning times
    • Service-friendly thanks to maintenance-free design and long service life of the backlighting display
  • Simple and user-friendly representation of process values thanks to, for example, input/output fields, vector graphics, trend curves, bar charts, text and bitmaps
  • Graphics library available with off-the-shelf picture objects
  • Can be used worldwide:
    • 32 languages can be configured (incl. Asian and Cyrillic character sets)
    • You can switch between up to 5 languages online
    • Language-dependent texts and graphics

Application

The SIMATIC HMI Basic Panels can be used wherever compact machines and plants are controlled and monitored locally, such as in production, process and building automation. They may be used in all kinds of industries and applications.

Design

The SIMATIC HMI Basic Panels are installation-compatible with the existing touch devices of the product family of Panels and Multi Panels.

KP300 Basic mono PN

  • 3.6″ FSTN pixel graphics, monochrome
  • 1 Ethernet interface (TCP/IP, PROFINET)
  • Touch device with 10 function keys and 10 system keys
  • Innovative successor to the Text Displays (TD 100C, TD 200/TD 200C, TD 400C) as well as the OP 73 and OP 73micro

KTP400 Basic mono PN

  • 3.8″ STN mono
  • 1 Ethernet interface (TCP/IP, PROFINET)
  • Touch screen and 4 tactile function keys

KTP400 Basic color PN

  • 4.3″ widescreen TFT display
  • 1 Ethernet interface (TCP/IP, PROFINET)
  • Touch screen and 4 tactile function keys

KP400 Basic color PN

  • 4.3″ widescreen TFT display
  • 1 Ethernet interface (TCP/IP, PROFINET)
  • Membrane keyboard with 8 function keys and 26 system keys
  • Innovative successor to the OP 77A

KTP600 Basic mono PN

  • 5.7″ STN mono
  • 1 Ethernet interface (TCP/IP, PROFINET)
  • Touch screen and 6 tactile function keys
  • Innovative successor to the TP 177micro/TP 177A

KTP600 Basic color PN or DP

  • 5.7″ TFT with 256 colors
  • 1 Ethernet interface (TCP/IP, PROFINET) or 1 RS 485/422 interface (MPI, PROFIBUS DP; separate version)
  • Touch screen and 6 tactile function keys
  • Innovative successor to the TP 177micro/TP 177A

KTP1000 Basic color PN or DP

  • 10.4″ TFT with 256 colors
  • Ethernet interface (TCP/IP, PROFINET) or 1 RS 485/422 interface (MPI, PROFIBUS DP; separate version)
  • Touch screen and 8 tactile function keys

TP1500 Basic color PN

  • 15.0″ TFT with 256 colors
  • 1 Ethernet interface (TCP/IP, PROFINET)
  • Touch screen

Function

  • Input/output fields
    for displaying and modifying process parameters
  • Buttons
    are used for direct triggering of functions and actions. Up to 16 functions can be configured simultaneously on buttons.
  • Graphics
    can be used as icons instead of text to “label” function keys or buttons. They can also be used as full-screen background images.
    The configuration tool contains a library with extensive graphics and diverse objects. All editors with an OLE interface (such as PaintShop, Designer or CorelDraw) can be used as graphics editors
  • Vector graphics
    Simple geometric basic forms (line, circle and rectangle) can be created direct in the configuring tool
  • Fixed texts
    for labeling function keys, process images and process values in different font sizes
  • Curve functions and bars
    are used for graphical display of dynamic values
  • Language switching:
    • 5 online languages, 32 configuration languages incl. Asian and Cyrillic character sets
    • Language-dependent texts and graphics
  • User administration (security) in accordance with the requirements of the different industries
    • Authentication with user ID and password
    • User-group-specific rights
  • Message system
    • Discrete messages
    • Analog messages
    • Freely-definable message classes (e.g. status/fault messages) for definition of acknowledgment response and display of message events
    • Message history
  • Recipe management
  • Help texts
    for process screens, messages and variables
  • Arithmetic functions
  • Limit value monitoring
    for reliable process control of inputs and outputs
  • Indicator light
    for indicating machine and plant statuses
  • Scheduler for global function execution in case of global events
  • Template concept for creation of screen templates (screen elements configured in the template appear in every screen)
  • Simple maintenance and configuration thanks to:
    • Backup/restore of configuration, operating system and firmware on/from a PC using ProSave
    • Configuration download via MPI/PROFIBUS DP or PROFINET
    • Automatic transfer identification
    • Individual contrast or brightness setting (except 6″ color) and calibration
    • Clean screen
    • No battery required

Configuration

The configuration is implemented using the engineering software SIMATIC WinCC Basic, Comfort, Professional or SIMATIC STEP 7 Basic (with integrated WinCC Basic).

The KTP400 Basic mono PN as well as all 6″ to 15″ devices can also be configured using the SIMATIC WinCC flexible Compact, Standard or Advanced engineering software.

Integration

The Basic Panels can be connected to:

  • SIMATIC S7 controllers
  • Non-Siemens controllers (applies for DP devices)
    • Allen Bradley DF1
    • Modicon Modbus RTU
    • Mitsubishi FX
    • Omron Hostlink/Multilink
  • Non-Siemens controllers (non-Siemens drivers for PN devices)
    • Allen Bradley Ethernet/IP
    • Modicon Modbus TCP/IP
    • Mitsubishi MC TCP/IP

Note:

For further information, see “System interfaces”.

Technical specifications

Article number 6AV6647-0AA11-3AX0 6AV6647-0AK11-3AX0 6AV6647-0AB11-3AX0 6AV6647-0AC11-3AX0
SIMATIC HMI KTP400 Basic mono PN SIMATIC HMI KTP400 Basic Color PN SIMATIC HMI KTP600 Basic mono PN SIMATIC HMI KTP600 Basic Color DP
General information
Product type designation KTP400 Basic mono PN KTP400 Basic color PN KTP600 Basic mono PN KTP600 Basic color DP
Display
Design of display STN TFT STN TFT
Screen diagonal 3.8 in 4.3 in 5.7 in 5.7 in
Display width 76.8 mm 95 mm 115.2 mm 115.2 mm
Display height 57.6 mm 53.8 mm 86.4 mm 86.4 mm
Number of colors 4; Grayscales 256 4; Grayscales 256
Resolution (pixels)
● Horizontal image resolution 320 Pixel 480 Pixel 320 Pixel 320 Pixel
● Vertical image resolution 240 Pixel 272 Pixel 240 Pixel 240 Pixel
Backlighting
● MTBF backlighting (at 25 °C) 30 000 h 50 000 h 50 000 h 50 000 h
● Backlight dimmable No No No No
Keyboard fonts
● Function keys
— Number of function keys 4 4 6 6
— Number of function keys with LEDs 0 0 0 0
● Keys with LED No No No No
● System keys No No No No
● Numeric keyboard Yes; Onscreen keyboard Yes; Onscreen keyboard Yes; Onscreen keyboard Yes; Onscreen keyboard
● alphanumeric keyboard Yes; Onscreen keyboard Yes; Onscreen keyboard Yes; Onscreen keyboard Yes; Onscreen keyboard
Touch operation
● Design as touch screen Yes Yes Yes Yes
Installation type/mounting
Mounting position vertical vertical vertical vertical
Mounting in portrait format possible Yes Yes Yes Yes
Mounting in landscape format possible Yes Yes Yes Yes
maximum permissible angle of inclination without external ventilation 35° 35° 35° 35°
Supply voltage
Type of supply voltage DC DC DC DC
Rated value (DC) 24 V 24 V 24 V 24 V
permissible range, lower limit (DC) 19.2 V 19.2 V 19.2 V 19.2 V
permissible range, upper limit (DC) 28.8 V 28.8 V 28.8 V 28.8 V
Input current
Current consumption (rated value) 0.1 A 0.1 A 0.24 A 0.35 A
Starting current inrush I²t 0.5 A²·s 0.5 A²·s 0.5 A²·s 0.5 A²·s
Power
Active power input, typ. 3 W 2 W 6 W 9 W
Processor
Processor type RISC 32 bit RISC 32 bit RISC 32 bit RISC 32 bit
Memory
Flash Yes Yes Yes Yes
RAM Yes Yes Yes Yes
Memory available for user data 1 Mbyte 1 Mbyte 1 Mbyte 1 Mbyte
Type of output
Acoustics
● Buzzer Yes Yes Yes Yes
● Speaker No No No No
Time of day
Clock
● Hardware clock (real-time) No No No No
● Software clock Yes Yes Yes Yes
● retentive No No No No
● synchronizable Yes Yes Yes Yes
Interfaces
Number of industrial Ethernet interfaces 1 1 1 0
Number of RS 485 interfaces 0 0 0 1
Number of RS 422 interfaces 0 0 0 1
Number of RS 232 interfaces 0 0 0 0
Number of USB interfaces 0 0 0 0
Number of 20 mA interfaces (TTY) 0 0 0 0
Number of parallel interfaces 0 0 0 0
Number of other interfaces 0 0 0 0
Number of SD card slots 0 0 0 0
With software interfaces No No No No
Industrial Ethernet
● Industrial Ethernet status LED 2 2 2 0
Protocols
PROFINET Yes Yes Yes No
Supports protocol for PROFINET IO No No No No
IRT No No No No
PROFIBUS No No No Yes
MPI No No No Yes
Protocols (Ethernet)
● TCP/IP Yes Yes Yes No
● DHCP Yes Yes Yes No
● SNMP Yes Yes Yes No
● DCP Yes Yes Yes No
● LLDP Yes Yes Yes No
WEB characteristics
● HTTP No No No No
● HTML No No No No
Further protocols
● CAN No No No No
● EtherNet/IP Yes Yes Yes No
● MODBUS Yes; Modicon (MODBUS TCP/IP) Yes; Modicon (MODBUS TCP/IP) Yes; Modicon (MODBUS TCP/IP) Yes; Modicon (MODBUS RTU)
Interrupts/diagnostics/status information
Diagnostic messages
● Diagnostic information readable No No No No
EMC
Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areas Yes
● Limit class B, for use in residential areas No
Degree and class of protection
IP (at the front) IP65 IP65 IP65 IP65
Enclosure Type 4 at the front Yes Yes Yes Yes
Enclosure Type 4x at the front Yes Yes Yes Yes
IP (rear) IP20 IP20 IP20 IP20
Standards, approvals, certificates
CE mark Yes Yes Yes Yes
cULus Yes Yes Yes Yes
RCM (formerly C-TICK) Yes Yes Yes Yes
KC approval Yes Yes Yes Yes
Use in hazardous areas
● ATEX Zone 2 No No No No
● ATEX Zone 22 No No No No
● cULus Class I Zone 1 No No No No
● cULus Class I Zone 2, Division 2 No No No No
● FM Class I Division 2 No No No No
Marine approval
● Germanischer Lloyd (GL) Yes Yes Yes Yes
● American Bureau of Shipping (ABS) Yes Yes Yes Yes
● Bureau Veritas (BV) Yes Yes Yes Yes
● Det Norske Veritas (DNV) Yes Yes Yes Yes
● Lloyds Register of Shipping (LRS) Yes Yes Yes Yes
● Nippon Kaiji Kyokai (Class NK) Yes Yes Yes Yes
● Polski Rejestr Statkow (PRS) Yes Yes Yes Yes
Ambient conditions
Ambient temperature during operation
● Operation (vertical installation)
— For vertical installation, min. 0 °C 0 °C 0 °C 0 °C
— For vertical installation, max. 50 °C 50 °C 50 °C 50 °C
● Operation (max. tilt angle)
— At maximum tilt angle, min. 0 °C 0 °C 0 °C 0 °C
— At maximum tilt angle, min. 40 °C 40 °C 40 °C 40 °C
● Operation (vertical installation, portrait format)
— For vertical installation, min. 0 °C 0 °C 0 °C 0 °C
— For vertical installation, max. 50 °C 40 °C 50 °C 50 °C
● Operation (max. tilt angle, portrait format)
— At maximum tilt angle, min. 0 °C 0 °C 0 °C 0 °C
— At maximum tilt angle, min. 40 °C 35 °C 40 °C 40 °C
Ambient temperature during storage/transportation
● min. -20 °C -20 °C -20 °C -20 °C
● max. 60 °C 60 °C 60 °C 60 °C
Relative humidity
● Operation, max. 90 %; no condensation 90 %; no condensation 90 %; no condensation 90 %; no condensation
Operating systems
proprietary Yes Yes Yes Yes
pre-installed operating system
● Windows CE No No No No
Configuration
Message indicator Yes Yes Yes Yes
Alarm system (incl. buffer and acknowledgment) Yes Yes Yes Yes
Process value display (output) Yes Yes Yes Yes
Process value default (input) possible Yes Yes Yes Yes
Recipe management Yes Yes Yes Yes
Configuration software
● STEP 7 Basic (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal)
● STEP 7 Professional (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal)
● WinCC flexible Compact Yes No Yes Yes
● WinCC flexible Standard Yes No Yes Yes
● WinCC flexible Advanced Yes No Yes Yes
● WinCC Basic (TIA Portal) Yes Yes Yes Yes
● WinCC Comfort (TIA Portal) Yes Yes Yes Yes
● WinCC Advanced (TIA Portal) Yes Yes Yes Yes
● WinCC Professional (TIA Portal) Yes Yes Yes Yes
Languages
Online languages
● Number of online/runtime languages 5 5 5 5
Project languages
● Languages per project 32 32 32 32
Functionality under WinCC (TIA Portal)
Libraries Yes Yes Yes Yes
Task planner
● time-controlled No No No No
● task-controlled Yes Yes Yes Yes
Help system Yes
● Number of characters per info text 320 320 320 320
Message system
● Number of alarm classes 32 32 32 32
● Bit messages
— Number of bit messages 200 200 200 200
● Analog messages
— Number of analog messages 15 15 15 15
● System messages HMI Yes Yes Yes Yes
● Number of characters per message 80 80 80 80
● Number of process values per message 8 8 8 8
● Message indicator Yes Yes Yes Yes
● Message buffer
— Number of entries 256 256 256 256
— Circulating buffer Yes Yes Yes Yes
— retentive Yes Yes Yes Yes
— maintenance-free Yes Yes Yes Yes
Recipe management
● Number of recipes 5 5 5 5
● Data records per recipe 20 20 20 20
● Entries per data record 20 20 20 20
● Size of internal recipe memory 40 kbyte 40 kbyte 40 kbyte 40 kbyte
● Recipe memory expandable No No No No
Variables
● Number of variables per device 250 500 500 500
● Number of variables per screen 30 30 30 30
● Limit values Yes Yes Yes Yes
● Multiplexing Yes Yes Yes Yes
● Structures No No No No
● Arrays Yes Yes Yes Yes
Images
● Number of configurable images 50 50 50 50
● Permanent window/default Yes Yes; No permanent window can be configured Yes Yes
● Global image Yes Yes Yes Yes
● Image selection by PLC Yes Yes Yes Yes
● Image number in the PLC Yes Yes Yes Yes
Image objects
● Number of objects per image 30 30 30 30
● Text fields Yes Yes Yes Yes
● I/O fields Yes Yes Yes Yes
● Graphic I/O fields (graphics list) Yes Yes Yes Yes
● Symbolic I/O fields (text list) Yes Yes Yes Yes
● Date/time fields Yes Yes Yes Yes
● Switches Yes Yes Yes Yes
● Buttons Yes Yes Yes Yes
● Graphic display Yes Yes Yes Yes
● Icons Yes Yes; Predefined screen objects Yes Yes
● Geometric objects Yes Yes Yes Yes
Complex image objects
● Number of complex objects per screen 5 5 5 5
● Alarm view Yes Yes Yes Yes
● Trend view Yes Yes Yes Yes
● User view Yes Yes Yes Yes
● Status/control No No No No
● Sm@rtClient view No No No No
● Recipe view Yes Yes Yes Yes
● f(x) trend view No No No No
● System diagnostics view No No No No
● Media Player No No No No
● Bar graphs Yes Yes Yes Yes
● Sliders No No No No
● Pointer instruments No No No No
● Analog/digital clock No No No No
Lists
● Number of text lists per project 150 150 150 150
● Number of entries per text list 30 30 30 30
● Number of graphics lists per project 100 100 100 100
● Number of entries per graphics list 30 30 30 30
Archiving
● Number of archives per device 0 0 0 0
Security
● Number of user groups 50 50 50 50
● Number of user rights 32 32 32 32
● Number of users 50 50 50 50
● Password export/import No No No No
● SIMATIC Logon No No No No
Character sets
● Keyboard fonts
— US English Yes Yes Yes Yes
Transfer (upload/download)
● MPI/PROFIBUS DP No No No Yes
● USB No No No No
● Ethernet Yes Yes Yes No
● using external storage medium No No No No
Process coupling
● S7-1200 Yes Yes Yes Yes
● S7-1500 Yes Yes Yes Yes
● S7-200 Yes Yes Yes Yes
● S7-300/400 Yes Yes Yes Yes
● LOGO! Yes Yes Yes Yes
● WinAC Yes No Yes Yes
● SINUMERIK No No No No
● SIMOTION No No No No
● Allen Bradley (EtherNet/IP) Yes Yes Yes No
● Allen Bradley (DF1) No No No Yes
● Mitsubishi (MC TCP/IP) Yes Yes Yes No
● Mitsubishi (FX) No No No Yes
● OMRON (FINS TCP) No No No No
● OMRON (LINK/Multilink) No No No Yes
● Modicon (Modbus TCP/IP) Yes Yes Yes No
● Modicon (Modbus) No No No Yes
Service tools/configuration aids
● Backup/Restore manually Yes Yes Yes Yes
● Backup/Restore automatically No No No No
● Simulation Yes Yes Yes Yes
● Device switchover Yes Yes Yes Yes
Peripherals/Options
Peripherals
● Printer No No No No
● SIMATIC HMI MM memory card: Multi Media Card No No No No
● SIMATIC HMI SD memory card: Secure Digital memory card No No No No
● USB memory No No No No
Mechanics/material
Enclosure material (front)
● Plastic Yes Yes Yes Yes
● Aluminum No No No No
● Stainless steel No No No No
Dimensions
Width of the housing front 140 mm 140 mm 214 mm 214 mm
Height of housing front 116 mm 116 mm 158 mm 158 mm
Mounting cutout, width 123 mm 123 mm 197 mm 197 mm
Mounting cutout, height 99 mm 99 mm 141 mm 141 mm
Overall depth 40 mm 33 mm 44 mm 44 mm
Weights
Weight without packaging 0.32 kg 0.34 kg 1.07 kg 1.07 kg
Weight incl. packaging 0.53 kg 0.45 kg 1.3 kg 1.35 kg

Article number 6AV6647-0AD11-3AX0 6AV6647-0AE11-3AX0 6AV6647-0AF11-3AX0
SIMATIC HMI KTP600 Basic Color PN SIMATIC HMI KTP1000 Basic Color DP SIMATIC HMI KTP1000 Basic Color PN
General information
Product type designation KTP600 Basic color PN KTP1000 Basic color DP KTP1000 Basic color PN
Display
Design of display TFT TFT TFT
Screen diagonal 5.7 in 10.4 in 10.4 in
Display width 115.2 mm 211.2 mm 211.2 mm
Display height 86.4 mm 158.4 mm 158.4 mm
Number of colors 256 256 256
Resolution (pixels)
● Horizontal image resolution 320 Pixel 640 Pixel 640 Pixel
● Vertical image resolution 240 Pixel 480 Pixel 480 Pixel
Backlighting
● MTBF backlighting (at 25 °C) 50 000 h 50 000 h 50 000 h
● Backlight dimmable No No No
Keyboard fonts
● Function keys
— Number of function keys 6 8 8
— Number of function keys with LEDs 0 0 0
● Keys with LED No No No
● System keys No No No
● Numeric keyboard Yes; Onscreen keyboard Yes; Onscreen keyboard Yes; Onscreen keyboard
● alphanumeric keyboard Yes; Onscreen keyboard Yes; Onscreen keyboard Yes; Onscreen keyboard
Touch operation
● Design as touch screen Yes Yes Yes
Installation type/mounting
Mounting position vertical vertical vertical
Mounting in portrait format possible Yes No No
Mounting in landscape format possible Yes Yes Yes
maximum permissible angle of inclination without external ventilation 35° 35° 35°
Supply voltage
Type of supply voltage DC DC DC
Rated value (DC) 24 V 24 V 24 V
permissible range, lower limit (DC) 19.2 V 19.2 V 19.2 V
permissible range, upper limit (DC) 28.8 V 28.8 V 28.8 V
Input current
Current consumption (rated value) 0.35 A 0.6 A 0.6 A
Starting current inrush I²t 0.5 A²·s 0.2 A²·s 0.2 A²·s
Power
Active power input, typ. 9 W 15 W 15 W
Processor
Processor type RISC 32 bit RISC 32 bit RISC 32 bit
Memory
Flash Yes Yes Yes
RAM Yes Yes Yes
Memory available for user data 1 Mbyte 2 Mbyte 2 Mbyte
Type of output
Acoustics
● Buzzer Yes Yes Yes
● Speaker No No No
Time of day
Clock
● Hardware clock (real-time) No No No
● Software clock Yes Yes Yes
● retentive No No No
● synchronizable Yes Yes Yes
Interfaces
Number of industrial Ethernet interfaces 1 0 1
Number of RS 485 interfaces 0 1 0
Number of RS 422 interfaces 0 1 0
Number of RS 232 interfaces 0 0 0
Number of USB interfaces 0 0 0
Number of 20 mA interfaces (TTY) 0 0 0
Number of parallel interfaces 0 0 0
Number of other interfaces 0 0 0
Number of SD card slots 0 0 0
With software interfaces No No No
Industrial Ethernet
● Industrial Ethernet status LED 2 0 2
Protocols
PROFINET Yes No Yes
Supports protocol for PROFINET IO No No No
IRT No No No
PROFIBUS No Yes No
MPI No Yes No
Protocols (Ethernet)
● TCP/IP Yes No Yes
● DHCP Yes No Yes
● SNMP Yes No Yes
● DCP Yes No Yes
● LLDP Yes No Yes
WEB characteristics
● HTTP No No No
● HTML No No No
Further protocols
● CAN No No No
● EtherNet/IP Yes No Yes
● MODBUS Yes; Modicon (MODBUS TCP/IP) Yes; Modicon (MODBUS RTU) Yes; Modicon (MODBUS TCP/IP)
Interrupts/diagnostics/status information
Diagnostic messages
● Diagnostic information readable No No No
Degree and class of protection
IP (at the front) IP65 IP65 IP65
Enclosure Type 4 at the front Yes Yes Yes
Enclosure Type 4x at the front Yes Yes Yes
IP (rear) IP20 IP20 IP20
Standards, approvals, certificates
CE mark Yes Yes Yes
cULus Yes Yes Yes
RCM (formerly C-TICK) Yes Yes Yes
KC approval Yes Yes Yes
Use in hazardous areas
● ATEX Zone 2 No No No
● ATEX Zone 22 No No No
● cULus Class I Zone 1 No No No
● cULus Class I Zone 2, Division 2 No No No
● FM Class I Division 2 No No No
Marine approval
● Germanischer Lloyd (GL) Yes Yes Yes
● American Bureau of Shipping (ABS) Yes Yes Yes
● Bureau Veritas (BV) Yes Yes Yes
● Det Norske Veritas (DNV) Yes Yes Yes
● Lloyds Register of Shipping (LRS) Yes Yes Yes
● Nippon Kaiji Kyokai (Class NK) Yes Yes Yes
● Polski Rejestr Statkow (PRS) Yes No No
Ambient conditions
Ambient temperature during operation
● Operation (vertical installation)
— For vertical installation, min. 0 °C 0 °C 0 °C
— For vertical installation, max. 50 °C 50 °C 50 °C
● Operation (max. tilt angle)
— At maximum tilt angle, min. 0 °C 0 °C 0 °C
— At maximum tilt angle, min. 40 °C 40 °C 40 °C
● Operation (vertical installation, portrait format)
— For vertical installation, min. 0 °C
— For vertical installation, max. 50 °C
● Operation (max. tilt angle, portrait format)
— At maximum tilt angle, min. 0 °C
— At maximum tilt angle, min. 40 °C
Ambient temperature during storage/transportation
● min. -30 °C -20 °C -20 °C
● max. 60 °C 60 °C 60 °C
Relative humidity
● Operation, max. 90 %; no condensation 90 %; no condensation 90 %; no condensation
Operating systems
proprietary Yes Yes Yes
pre-installed operating system
● Windows CE No No No
Configuration
Message indicator Yes Yes Yes
Alarm system (incl. buffer and acknowledgment) Yes Yes Yes
Process value display (output) Yes Yes Yes
Process value default (input) possible Yes Yes Yes
Recipe management Yes Yes Yes
Configuration software
● STEP 7 Basic (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal)
● STEP 7 Professional (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal)
● WinCC flexible Compact Yes Yes Yes
● WinCC flexible Standard Yes Yes Yes
● WinCC flexible Advanced Yes Yes Yes
● WinCC Basic (TIA Portal) Yes Yes Yes
● WinCC Comfort (TIA Portal) Yes Yes Yes
● WinCC Advanced (TIA Portal) Yes Yes Yes
● WinCC Professional (TIA Portal) Yes Yes Yes
Languages
Online languages
● Number of online/runtime languages 5 5 5
Project languages
● Languages per project 32 32 32
Functionality under WinCC (TIA Portal)
Libraries Yes Yes Yes
Task planner
● time-controlled No No No
● task-controlled Yes Yes Yes
Help system
● Number of characters per info text 320
Message system
● Number of alarm classes 32 32 32
● Bit messages
— Number of bit messages 200 200 200
● Analog messages
— Number of analog messages 15 15 15
● System messages HMI Yes Yes Yes
● Number of characters per message 80 80 80
● Number of process values per message 8 8 8
● Message indicator Yes Yes Yes
● Message buffer
— Number of entries 256 256 256
— Circulating buffer Yes Yes Yes
— retentive Yes Yes Yes
— maintenance-free Yes Yes Yes
Recipe management
● Number of recipes 5 5 5
● Data records per recipe 20 20 20
● Entries per data record 20 20 20
● Size of internal recipe memory 40 kbyte 40 kbyte 40 kbyte
● Recipe memory expandable No No No
Variables
● Number of variables per device 500 500 500
● Number of variables per screen 30 30 30
● Limit values Yes Yes Yes
● Multiplexing Yes Yes Yes
● Structures No No No
● Arrays Yes Yes Yes
Images
● Number of configurable images 50 50 50
● Permanent window/default Yes Yes Yes
● Global image Yes Yes Yes
● Image selection by PLC Yes Yes Yes
● Image number in the PLC Yes Yes Yes
Image objects
● Number of objects per image 30 30 30
● Text fields Yes Yes Yes
● I/O fields Yes Yes Yes
● Graphic I/O fields (graphics list) Yes Yes Yes
● Symbolic I/O fields (text list) Yes Yes Yes
● Date/time fields Yes Yes Yes
● Switches Yes Yes Yes
● Buttons Yes Yes Yes
● Graphic display Yes Yes Yes
● Icons Yes Yes Yes
● Geometric objects Yes Yes Yes
Complex image objects
● Number of complex objects per screen 5 5 5
● Alarm view Yes Yes Yes
● Trend view Yes Yes Yes
● User view Yes Yes Yes
● Status/control No No No
● Sm@rtClient view No No No
● Recipe view Yes Yes Yes
● f(x) trend view No No No
● System diagnostics view No No No
● Media Player No No No
● Bar graphs Yes Yes Yes
● Sliders No No No
● Pointer instruments No No No
● Analog/digital clock No No No
Lists
● Number of text lists per project 150 150 150
● Number of entries per text list 30 30 30
● Number of graphics lists per project 100 100 100
● Number of entries per graphics list 30 30 30
Archiving
● Number of archives per device 0 0 0
Security
● Number of user groups 50 50 50
● Number of user rights 32 32 32
● Number of users 50 50 50
● Password export/import No No No
● SIMATIC Logon No No No
Character sets
● Keyboard fonts
— US English Yes Yes Yes
Transfer (upload/download)
● MPI/PROFIBUS DP No Yes No
● USB No No No
● Ethernet Yes No Yes
● using external storage medium No No No
Process coupling
● S7-1200 Yes Yes Yes
● S7-1500 Yes Yes Yes
● S7-200 Yes Yes Yes
● S7-300/400 Yes Yes Yes
● LOGO! Yes Yes Yes
● WinAC Yes Yes Yes
● SINUMERIK No No No
● SIMOTION No No No
● Allen Bradley (EtherNet/IP) Yes No Yes
● Allen Bradley (DF1) No Yes No
● Mitsubishi (MC TCP/IP) Yes No Yes
● Mitsubishi (FX) No Yes No
● OMRON (FINS TCP) No No No
● OMRON (LINK/Multilink) No Yes No
● Modicon (Modbus TCP/IP) Yes No Yes
● Modicon (Modbus) No Yes Yes
Service tools/configuration aids
● Backup/Restore manually Yes Yes Yes
● Backup/Restore automatically No No No
● Simulation Yes Yes Yes
● Device switchover Yes Yes Yes
Peripherals/Options
Peripherals
● Printer No No No
● SIMATIC HMI MM memory card: Multi Media Card No No No
● SIMATIC HMI SD memory card: Secure Digital memory card No No No
● USB memory No No No
Mechanics/material
Enclosure material (front)
● Plastic Yes Yes Yes
● Aluminum No No No
● Stainless steel No No No
Dimensions
Width of the housing front 214 mm 335 mm 335 mm
Height of housing front 158 mm 275 mm 275 mm
Mounting cutout, width 197 mm 310 mm 310 mm
Mounting cutout, height 141 mm 248 mm 248 mm
Overall depth 44 mm 60 mm 60 mm
Weights
Weight without packaging 1.07 kg 2.65 kg 2.65 kg
Weight incl. packaging 1.32 kg 3.52 kg 3.38 kg

Article number 6AV6647-0AH11-3AX0 6AV6647-0AJ11-3AX0 6AV6647-0AG11-3AX0
SIMATIC HMI KP300 Basic mono PN SIMATIC HMI KP400 Basic Color PN SIMATIC HMI TP1500 Basic Color PN
General information
Product type designation KP300 Basic mono PN KP400 Basic color PN TP1500 Basic color PN
Display
Design of display FSTN TFT TFT
Screen diagonal 3.6 in 4.3 in 15 in
Display width 87 mm 95 mm 304.1 mm
Display height 31 mm 53.8 mm 228.1 mm
Number of colors 4; Backlit display only (white, red, green, yellow) 256 256
Resolution (pixels)
● Horizontal image resolution 240 Pixel 480 Pixel 1 024 Pixel
● Vertical image resolution 80 Pixel 272 Pixel 768 Pixel
Backlighting
● MTBF backlighting (at 25 °C) 50 000 h 50 000 h 50 000 h
● Backlight dimmable No No No
Keyboard fonts
● Function keys
— Number of function keys 10 8 0
— Number of function keys with LEDs 0 0 0
● Keys with LED No No No
● System keys Yes Yes No
● Numeric keyboard Yes; Keyboard Yes; Keyboard Yes; Onscreen keyboard
● alphanumeric keyboard Yes; Keyboard Yes; similar to mobile phone Yes; Onscreen keyboard
Touch operation
● Design as touch screen No No Yes
Installation type/mounting
Mounting position vertical vertical vertical
Mounting in portrait format possible No No No
Mounting in landscape format possible Yes Yes Yes
maximum permissible angle of inclination without external ventilation 35° 35° 35°
Supply voltage
Type of supply voltage DC DC DC
Rated value (DC) 24 V 24 V 24 V
permissible range, lower limit (DC) 19.2 V 19.2 V 19.2 V
permissible range, upper limit (DC) 28.8 V 28.8 V 28.8 V
Input current
Current consumption (rated value) 0.1 A 0.1 A 0.8 A
Starting current inrush I²t 0.5 A²·s 0.5 A²·s 0.2 A²·s
Power
Active power input, typ. 3 W 2 W 20 W
Processor
Processor type RISC 32 bit RISC 32 bit RISC 32 bit
Memory
Flash Yes Yes Yes
RAM Yes Yes Yes
Memory available for user data 1 Mbyte 1 Mbyte 2 Mbyte
Type of output
Acoustics
● Buzzer No No Yes
● Speaker No No No
Time of day
Clock
● Hardware clock (real-time) No No No
● Software clock Yes Yes Yes
● retentive No No No
● synchronizable Yes Yes Yes
Interfaces
Number of industrial Ethernet interfaces 1 1 1
Number of RS 485 interfaces 0 0 0
Number of RS 422 interfaces 0 0 0
Number of RS 232 interfaces 0 0 0
Number of USB interfaces 0 0 0
Number of 20 mA interfaces (TTY) 0 0 0
Number of parallel interfaces 0 0 0
Number of other interfaces 0 0 0
Number of SD card slots 0 0 0
With software interfaces No No No
Industrial Ethernet
● Industrial Ethernet status LED 2 2 2
Protocols
PROFINET Yes Yes Yes
Supports protocol for PROFINET IO No No No
IRT No No No
PROFIBUS No No No
MPI No No No
Protocols (Ethernet)
● TCP/IP Yes Yes Yes
● DHCP Yes Yes Yes
● SNMP Yes Yes Yes
● DCP Yes Yes Yes
● LLDP Yes Yes Yes
WEB characteristics
● HTTP No No No
● HTML No No No
Further protocols
● CAN No No No
● EtherNet/IP Yes Yes Yes
● MODBUS Yes; Modicon (MODBUS TCP/IP) Yes; Modicon (MODBUS TCP/IP) Yes; Modicon (MODBUS TCP/IP)
Interrupts/diagnostics/status information
Diagnostic messages
● Diagnostic information readable No No
EMC
Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areas Yes Yes
● Limit class B, for use in residential areas No No
Degree and class of protection
IP (at the front) IP65 IP65 IP65
Enclosure Type 4 at the front Yes Yes Yes
Enclosure Type 4x at the front Yes Yes Yes
IP (rear) IP20 IP20 IP20
Standards, approvals, certificates
CE mark Yes Yes Yes
cULus Yes Yes Yes
RCM (formerly C-TICK) Yes Yes Yes
KC approval Yes Yes Yes
Use in hazardous areas
● ATEX Zone 2 No No No
● ATEX Zone 22 No No No
● cULus Class I Zone 1 No No No
● cULus Class I Zone 2, Division 2 Yes No No
● FM Class I Division 2 No No No
Marine approval
● Germanischer Lloyd (GL) Yes No No
● American Bureau of Shipping (ABS) Yes No No
● Bureau Veritas (BV) Yes No No
● Det Norske Veritas (DNV) Yes No No
● Lloyds Register of Shipping (LRS) Yes No No
● Nippon Kaiji Kyokai (Class NK) Yes No No
● Polski Rejestr Statkow (PRS) No No No
Ambient conditions
Ambient temperature during operation
● Operation (vertical installation)
— For vertical installation, min. 0 °C 0 °C 0 °C
— For vertical installation, max. 50 °C 50 °C 50 °C
● Operation (max. tilt angle)
— At maximum tilt angle, min. 0 °C 0 °C 0 °C
— At maximum tilt angle, min. 40 °C 40 °C 40 °C
Ambient temperature during storage/transportation
● min. -20 °C -20 °C -20 °C
● max. 60 °C 60 °C 60 °C
Relative humidity
● Operation, max. 90 %; no condensation 90 %; no condensation 90 %; no condensation
Operating systems
proprietary Yes Yes Yes
pre-installed operating system
● Windows CE No No No
Configuration
Message indicator Yes Yes Yes
Alarm system (incl. buffer and acknowledgment) Yes Yes Yes
Process value display (output) Yes Yes Yes
Process value default (input) possible Yes Yes Yes
Recipe management Yes Yes Yes
Configuration software
● STEP 7 Basic (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal)
● STEP 7 Professional (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal)
● WinCC flexible Compact No No Yes
● WinCC flexible Standard No No Yes
● WinCC flexible Advanced No No Yes
● WinCC Basic (TIA Portal) Yes Yes Yes
● WinCC Comfort (TIA Portal) Yes Yes Yes
● WinCC Advanced (TIA Portal) Yes Yes Yes
● WinCC Professional (TIA Portal) Yes Yes Yes
Languages
Online languages
● Number of online/runtime languages 5 5 5
Project languages
● Languages per project 32 32 32
Functionality under WinCC (TIA Portal)
Libraries Yes Yes Yes
Task planner
● time-controlled No No No
● task-controlled Yes Yes Yes
Help system Yes Yes
● Number of characters per info text 320 320
Message system
● Number of alarm classes 32 32 32
● Bit messages
— Number of bit messages 200 200 200
● Analog messages
— Number of analog messages 15 15 15
● System messages HMI Yes Yes Yes
● Number of characters per message 80 80 80
● Number of process values per message 8 8 8
● Message indicator Yes Yes Yes
● Message buffer
— Number of entries 256 256 256
— Circulating buffer Yes Yes Yes
— retentive Yes Yes Yes
— maintenance-free Yes Yes Yes
Recipe management
● Number of recipes 5 5 5
● Data records per recipe 20 20 20
● Entries per data record 20 20 20
● Size of internal recipe memory 40 kbyte 40 kbyte 40 kbyte
● Recipe memory expandable No No No
Variables
● Number of variables per device 250 500 500
● Number of variables per screen 30 30 30
● Limit values Yes Yes Yes
● Multiplexing Yes Yes Yes
● Structures No No No
● Arrays Yes Yes Yes
Images
● Number of configurable images 50 50 50
● Permanent window/default Yes Yes; No permanent window can be configured Yes
● Global image Yes Yes Yes
● Image selection by PLC Yes Yes Yes
● Image number in the PLC Yes Yes Yes
Image objects
● Number of objects per image 30 30 30
● Text fields Yes Yes Yes
● I/O fields Yes Yes Yes
● Graphic I/O fields (graphics list) Yes Yes Yes
● Symbolic I/O fields (text list) Yes Yes Yes
● Date/time fields Yes Yes Yes
● Switches Yes Yes Yes
● Buttons Yes Yes Yes
● Graphic display Yes Yes Yes
● Icons Yes Yes; Predefined screen objects Yes
● Geometric objects Yes Yes Yes
Complex image objects
● Number of complex objects per screen 5 5 5
● Alarm view Yes Yes Yes
● Trend view Yes Yes Yes
● User view Yes Yes Yes
● Status/control No No No
● Sm@rtClient view No No No
● Recipe view Yes Yes Yes
● f(x) trend view No No No
● System diagnostics view No No No
● Media Player No No No
● Bar graphs Yes Yes Yes
● Sliders No No No
● Pointer instruments No No No
● Analog/digital clock No No No
Lists
● Number of text lists per project 150 150 150
● Number of entries per text list 30 30 30
● Number of graphics lists per project 100 100 100
● Number of entries per graphics list 30 30 30
Archiving
● Number of archives per device 0 0 0
Security
● Number of user groups 50 50 50
● Number of user rights 32 32 32
● Number of users 50 50 50
● Password export/import No No No
● SIMATIC Logon No No No
Character sets
● Keyboard fonts
— US English Yes Yes Yes
Transfer (upload/download)
● MPI/PROFIBUS DP No No No
● USB No No No
● Ethernet Yes Yes Yes
● using external storage medium No No No
Process coupling
● S7-1200 Yes Yes Yes
● S7-1500 Yes Yes Yes
● S7-200 Yes Yes Yes
● S7-300/400 Yes Yes Yes
● LOGO! Yes Yes Yes
● WinAC Yes No Yes
● SINUMERIK No No No
● SIMOTION No No No
● Allen Bradley (EtherNet/IP) Yes Yes Yes
● Allen Bradley (DF1) No No No
● Mitsubishi (MC TCP/IP) Yes Yes Yes
● Mitsubishi (FX) No No No
● OMRON (FINS TCP) No No No
● OMRON (LINK/Multilink) No No No
● Modicon (Modbus TCP/IP) Yes Yes Yes
● Modicon (Modbus) No No Yes
Service tools/configuration aids
● Backup/Restore manually Yes Yes Yes
● Backup/Restore automatically No No No
● Simulation Yes Yes Yes
● Device switchover Yes Yes Yes
Peripherals/Options
Peripherals
● Printer No No No
● SIMATIC HMI MM memory card: Multi Media Card No No No
● SIMATIC HMI SD memory card: Secure Digital memory card No No No
● USB memory No No No
Mechanics/material
Enclosure material (front)
● Plastic Yes Yes Yes
● Aluminum No No No
● Stainless steel No No No
Dimensions
Width of the housing front 165 mm 162 mm 400 mm
Height of housing front 97 mm 189 mm 310 mm
Mounting cutout, width 149 mm 135 mm 367 mm
Mounting cutout, height 82 mm 171 mm 289 mm
Overall depth 30 mm 33 mm 60 mm
Weights
Weight without packaging 0.25 kg 0.51 kg 4.2 kg
Weight incl. packaging 0.38 kg 0.66 kg 4.68 kg

Dimensional drawings

All dimensions in mm. For installation cutout, see technical specifications.

KP300 Basic

KTP400 Basic mono PN

KTP400 Basic color PN

KP400 Basic

KTP600 Basic

KTP1000 Basic

TP1500 Basic

Key Panels
Key Panels
Unified Basic Panels
Unified Basic Panels
Basic Panels (2nd Generation)
Basic Panels (2nd Generation)
Unified Comfort Panels
Unified Comfort Panels
Unified Comfort Panel Pro
Unified Comfort Panel Pro
Comfort Panels
Comfort Panels
Comfort Panel Pro
Comfort Panel Pro
Mobile Panels 2nd Generation
Mobile Panels 2nd Generation
TIA Portal - WinCC
TIA Portal - WinCC

Did you know, we are an entrusted Siemens approved partner?

Loading...